General
Net weight | 1.1 kg |
---|---|
Operating voltage display | Green LED |
Efficiency | > 93 % (at 400 V AC and nominal values) |
Insulation voltage input/output | 4 kV AC (type test) |
2 kV AC (routine test) | |
Protection class | I |
MTBF (IEC 61709, SN 29500) | > 633000 h (40°C) |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | Alignable: 5 mm horizontally, 15 mm next to active components, 50 mm vertically |
Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
Low Voltage Directive | Conformance with LV directive 2006/95/EC |
Standard – Electrical equipment of machines | EN 60204 |
Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
Shipbuilding approval | Germanischer Lloyd (EMC 1), ABS, LR, RINA, NK, DNV, BV |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204 (PELV) |
Standard - Safe isolation | DIN VDE 0100-410 |
DIN VDE 0106-1010 | |
Standard – Protection against electric shock | DIN 57100-410 |
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | DIN VDE 0106-101 |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Standard - Equipment safety | GS (tested safety) |
Approval - requirement of the semiconductor industry with regard to mains voltage dips | SEMI F47-0706 Compliance Certificate |
Information technology equipment - safety (CB scheme) | CB Scheme |
UL approvals | UL Listed UL 508 |
UL/C-UL Recognized UL 60950-1 (3-wire + PE, star net) | |
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
Surge voltage category | III |